Operating Parameters Set Up
E-S 500 / 502 Classic Series Instruction Manual
4.3
PUSH 1 or PUSH 2 to increase or decrease the parameter. Then press SET button to move
to the next parameter.
1. Press SET button to begin.
2. LED shows P1: P1 is for setting your run time. The run time will be determined from the
time you had determined during the set up of the limit switches. Take that determined
run time and add 1 second. So if it takes 10 seconds to get from closed to open
between limit switches; set the run time to 11 seconds. The options are 0-99 seconds.
3. LED shows P2: P2 is for setting your slow down time. The gate opener will slow down to
half speed after the time set on P2 expires. If you wish to have the gate open and close
faster make the slow down start time a longer period of time. If you want to put less stress
on the gears and gate set the slow time shorter to slow the momentum sooner. The
options will adjust to match the previously set run time. NOTE: motor must be in slow
down to detect limits—be sure this number does not exceed the time the motor take to
move from one limit to the other.
4. LED shows P3: P3 is the force setting, the lower the number the easier the gate will
reverse directions when it meets resistance. This number may have to be changed to a
higher setting if your gate is obstructing unexpectedly. The number should be set to the
highest number during initial setup and reduced to the point of reliable operation that
takes into account change in gate resistance through out the year. The options are
0-32.
5. LED shows P4: P4 is for setting a delay between leafs if you have overlapping gates or
a gate lock. The motor wired into the master terminals (1) opens first if there is a delay
and closes second. It is recommended to have a delay of 3 seconds to avoid any
coming issues between leaves.
6. LED shows P5: P5 is the delay for automatic re-close from the open position this
option needs to be turned on using the dip switch on the board. The options are 0-99
seconds.
7. LED shows P6: P6 is the release for the gate lock – this option determines the length of
time 24VDC will be sent out of terminals E_LOCK. The options are 1-4 seconds.
8. Press SET to finish. You should hear 3 beeps; this indicates parameter programming is
finished.